Top-mounted cooling units 1500 – 2000 W

Top-mounted cooling units 1500 – 2000 W

Specification:

  • Housing material: steel sheet/stainless steel
  • Color: RAL 7035
  • Refrigerant: R134a
  • Protection degree:
    • Cabinet air circuit: IP54
    • Ambient air circuit: IP24
  • Certification: CE

Supply includes:

  • Unit ready for connection.
Where to buy
Print Favorities E-mail Twitter RSS
  • top mounted cooling unit 1500-2000 WAirflow top mounted cooling unit 1500-2000 W
Top-mounted cooling units, cooling capacity 1500 W     
Order code   AC-TM3-15-4000 AC-TM3-15-6000 AC-TM3-15-4200 AC-TM3-15-6200
Material   Steel sheet Steel sheet Stainless steel Stainless steel
Dimensions mm H 410 410 410 410
  W 600 600 600 600
  D 400 400 400 400
Voltage/Frequency  

230 V

50/60 Hz ~N

400 - 460 V

50/60 Hz 3~

230 V

50/60 Hz ~N

400 - 460 V

50/60 Hz 3~

Cooling capacity to DIN 3168  L35 L35 1500 W 1500 W 1500 W 1500 W
L35 L50 950 W 950 W 950 W 950 W
Power Consumption L35 L35 1200 W 1200 W 1200 W 1200 W
Max. air volume flow Ambient air circuit 860 m3/h 860 m3/h 860 m3/h 860 m3/h
  Cabinet air circuit 540 m3/h 540 m3/h 540 m3/h 540 m3/h
Rated current   5,3 A 3 A 5,3 A 3 A
Starting current   22 A 15 A 22 A 15 A
Pre-Fuse T   10 A 3 x 6 A 10 A 3 x 6 A
Operating temperature range   +20°C to +55°C +20°C to +55°C +20°C to +55°C +20°C to +55°C
Weight   58 kg 58 kg 58 kg 58 kg
Compressor   Rotary piston Rotary piston Rotary piston Rotary piston
Connection   Connection terminals Connection terminals Connection terminals Connection terminals
Other input voltage options available upon request. 400 V-3phase units do not need additional MP.         

           
Top-mounted cooling units, cooling capacity 2000 W     
Order code   AC-TM3-20-4000 AC-TM3-20-6000 AC-TM3-20-4200 AC-TM3-20-6200
Material   Steel sheet Steel sheet Stainless steel Stainless steel
Dimensions mm H 410 410 410 410
  W 600 600 600 600
  D 400 400 400 400
Voltage/Frequency  

230 V

50/60 Hz ~N

400 - 460 V

50/60 Hz 3~

230 V

50/60 Hz ~N

400 - 460 V

50/60 Hz 3~

Cooling capacity to DIN 3168  L35 L35 2000 W 2000 W 2000 W 2000 W
L35 L50 1250 W 1250 W 1250 W 1250 W
Power Consumption L35 L35 1600 W 1500 W 1600 W 1500 W
Max. air volume flow Ambient air circuit 750 m3/h 750 m3/h 750 m3/h 750 m3/h
  Cabinet air circuit 540 m3/h 540 m3/h 540 m3/h 540 m3/h
Rated current   7 A 3,7 A 7 A 3,7 A
Starting current   33,5 A 20 A 33,5 A 20 A
Pre-Fuse T   10 A 3 x 6 A 10 A 3 x 6 A
Operating temperature range   +20°C to +55°C +20°C to +55°C +20°C to +55°C +20°C to +55°C
Weight   63 kg 63 kg 63 kg 63 kg
Compressor   Rotary piston Rotary piston Rotary piston Rotary piston
Connection   Connection terminals Connection terminals Connection terminals Connection terminals
Other input voltage options available upon request. 400 V-3phase units do not need additional MP.     
File type Language version

  • Catalog Climate Control Solutions (PDF - 8.07MB)
    cs  en