CoolTop

CoolTop

CoolTop represents a family of precision cooling units specifically designed for installation on top of IT racks in server rooms and large data centers. An ideal cooling system for Conteg-contained IT rack aisles. Unique solution for IT environments without occupied floor area in data centers.

SUITABLE FOR:

  • Any type of data center
  • Applications with large amounts of floor space
  • Clients focused on saving energy

 

MAIN FEATURES:

Effective use of data center floor space

  • Cooling systems with Cooltop units occupy zero floor area
  • Raised floor unneccesary for air distribution

Very low power consumption

  • Set of highly-efficient fans with EC technology motors
  • Perfect airflow control
  • Optimized heat exchanger and interior aerodynamics
  • Recommended pressure control

Perfect project adaptability

  • Easy grouping of CoolTop units to meet requested capacities
  • Ideal for contained hot or cold aisles

 

Where to buy
Print Favorities E-mail Twitter RSS
  • CoolTopCoolTopCoolTopCoolTop2CoolTop2CoolTop3
 CoolTeg Plus CW
    CoolTop2 CoolTop3
Indoor unit code Unit AC-TOP2-CW-240/60 AC-TCW-42-30/XX-XXX
Connected outdoor unit code   Chilled water system
BASIC DATA
Cooling system – Chilled water
Architecture – Open Open
Nominal cooling capacity1 kW 37.0 48.0
Nominal net cooling capacity2 kW 36.3 46.9
Power supply V/ph/Hz 230/1/50
Running current A 3.4 5.0
Maximum current A 4.6 6.8
Nominal power consumption W 710 1100
Nominal airflow3 m3/h 7700 11000
Number of fans Pcs 2 3
Motor fan technology – EC
Water flow kg/h 6200 8200
Filter class – G2 (+ droplet separator)
DIMENSIONS
Height4 mm (U) 600
Width mm 2400
Depth6 mm 400 (600)
Weight6 kg 175 184
PIPING CONNECTION
Supply pipe diameter and type – 6/4" female
Return pipe diameter and type – 6/4" female

1 Cooling capacity can be changed via electronic controller. Nominal cooling capacity is stated for airtemperature of 35 °C in hot zone, without condensation (relative humidity under dew point). Watertemperature is 10/15 °C, clean filters.

2 Net cooling capacity (without heat from fans) is usable cooling capacity of entire system

3 Airflow is changed by control needs. Nominal airflow equals nominal cooling capacity.

4 Without any base frame

5 Bottom side length 400 mm; top side length 600 mm

6 For weight with droplet separator, add 11 kg

File type Language version

  • Cooling Brochure (PDF - 0.59MB)
    de  en  fr  ru   
  • Technical Datasheet CoolTop (PDF - 1.29MB)
    cs  de  en  fr  ru   
  • Datasheet CoolTop (PDF - 0.54MB)
    en   

Datasheet:

Datasheet_CoolTop